352 sq ft · 200 lux target

16×22 laundry:
15 lights

15 fixtures A 16×22 ft laundry (352 sq ft) needs approximately 15 recessed lights at 800 lumens each — about 12,383 lumens in total — laid out 5 across by 3 deep.

Space them 4.4 ft apart along the 22 ft wall and 5.3 ft apart along the 16 ft wall, starting 2.2 ft from the end walls.

Fixtures15at 800 lm each
Total lumens12,383to hit 200 lux
Spacing4.4′× 5.3′ apart
Wall offset2.2′from the end wall

The ceiling plan

Drawn to scale, with each fixture at its computed position and the pale circles showing roughly where each one lands on the working plane.

22 ft 16 ft 5 across × 3 deep · 4.4 ft × 5.3 ft apart · 2.2 ft from the end walls

Same room, different fixtures

If you have already chosen a fitting, read across from its lumen output.

Fixture outputRough equivalentFixtures neededSuggested grid
450 lm 40 W incandescent 306 × 5
650 lm 50 W incandescent 205 × 4
800 lm 60 W incandescent 155 × 3
1000 lm 75 W incandescent 124 × 3
1200 lm 100 W incandescent 124 × 3

Fewer, brighter fixtures give more contrast; more, dimmer fixtures give flatter, more even light. Both rows deliver the same total.

How the 15 was calculated

Target illuminance for a laundry200 luxpublished range 200–300 lux
Floor area32.7 m²352 sq ft
Mounting height above the working plane5 ft8 ft ceiling, 3.0 ft working plane
Room index1.84(L × W) ÷ (Hm × (L + W))
Utilisation factor0.66from the room index, light surfaces
Maintenance factor0.8dirt and lamp depreciation
Lumens required12,383 lm200 × 32.7 ÷ (0.66 × 0.8)
Fixtures at 800 lm15delivering about 194 lux

A working room. Treat it closer to a kitchen than to a hallway.

Other ceiling heights

CeilingFixturesGridSpacingMax spacing
8 ft155 × 34.4′ × 5.3′6.6′
9 ft164 × 45.5′ × 4′7.9′
10 ft205 × 44.4′ × 4′9.2′
12 ft205 × 44.4′ × 4′11.8′

Questions

How many recessed lights do I need for a 16x22 laundry?

About 15 fixtures at 800 lumens each, arranged 5 across by 3 deep. That gives roughly 194 lux across 352 square feet, against a target of 200 lux for a laundry.

How many lumens does a 16x22 laundry need?

Roughly 12,383 lumens in total. That comes from 200 lux over 32.7 m², divided by a utilisation factor of 0.66 and a maintenance factor of 0.8 — the light that never reaches the working plane has to be paid for up front.

How far apart should the lights be in a 16x22 room?

4.4 ft apart along the 22 ft wall and 5.3 ft apart along the 16 ft wall, with the outer row about 2.2 ft in from the end walls — half a spacing. With a 8 ft ceiling the maximum sensible spacing is around 6.6 ft before the floor starts to show scallops.

Does the ceiling height change the answer?

Yes, in two ways. A higher ceiling spreads each fixture's light over a wider area, so fixtures can sit further apart — but it also drops the light level reaching the floor, so a taller room generally needs more total lumens. At 8 ft the room index works out at 1.84, giving a utilisation factor of 0.66.

Computed with the lumen method — see how it works and where it is weak. Planning guidance only, not an electrical design. Fixture counts are a starting point — follow your local wiring rules and use a licensed electrician for the installation.