252 sq ft · 400 lux target

14×18 workshop:
24 lights

24 fixtures A 14×18 ft workshop (252 sq ft) needs approximately 24 recessed lights at 800 lumens each — about 18,663 lumens in total — laid out 6 across by 4 deep.

Space them 3 ft apart along the 18 ft wall and 3.5 ft apart along the 14 ft wall, starting 1.5 ft from the end walls.

Fixtures24at 800 lm each
Total lumens18,663to hit 400 lux
Spacing3′× 3.5′ apart
Wall offset1.5′from the end wall

The ceiling plan

Drawn to scale, with each fixture at its computed position and the pale circles showing roughly where each one lands on the working plane.

18 ft 14 ft 6 across × 4 deep · 3 ft × 3.5 ft apart · 1.5 ft from the end walls

Same room, different fixtures

If you have already chosen a fitting, read across from its lumen output.

Fixture outputRough equivalentFixtures neededSuggested grid
450 lm 40 W incandescent 427 × 6
650 lm 50 W incandescent 306 × 5
800 lm 60 W incandescent 246 × 4
1000 lm 75 W incandescent 205 × 4
1200 lm 100 W incandescent 164 × 4

Fewer, brighter fixtures give more contrast; more, dimmer fixtures give flatter, more even light. Both rows deliver the same total.

How the 24 was calculated

Target illuminance for a workshop400 luxpublished range 500–750 lux
Floor area23.4 m²252 sq ft
Mounting height above the working plane5 ft8 ft ceiling, 3.0 ft working plane
Room index1.56(L × W) ÷ (Hm × (L + W))
Utilisation factor0.63from the room index, light surfaces
Maintenance factor0.8dirt and lamp depreciation
Lumens required18,663 lm400 × 23.4 ÷ (0.63 × 0.8)
Fixtures at 800 lm24delivering about 412 lux

The highest requirement here. The ceiling is sized to 400 lux with task lighting assumed over the bench — machine and detail work needs both quantity and good colour rendering.

Other ceiling heights

CeilingFixturesGridSpacingMax spacing
8 ft246 × 43′ × 3.5′6.6′
9 ft246 × 43′ × 3.5′7.9′
10 ft255 × 53.6′ × 2.8′9.2′
12 ft306 × 53′ × 2.8′11.8′

Questions

How many recessed lights do I need for a 14x18 workshop?

About 24 fixtures at 800 lumens each, arranged 6 across by 4 deep. That gives roughly 412 lux across 252 square feet, against a target of 400 lux for a workshop.

How many lumens does a 14x18 workshop need?

Roughly 18,663 lumens in total. That comes from 400 lux over 23.4 m², divided by a utilisation factor of 0.63 and a maintenance factor of 0.8 — the light that never reaches the working plane has to be paid for up front.

How far apart should the lights be in a 14x18 room?

3 ft apart along the 18 ft wall and 3.5 ft apart along the 14 ft wall, with the outer row about 1.5 ft in from the end walls — half a spacing. With a 8 ft ceiling the maximum sensible spacing is around 6.6 ft before the floor starts to show scallops.

Does the ceiling height change the answer?

Yes, in two ways. A higher ceiling spreads each fixture's light over a wider area, so fixtures can sit further apart — but it also drops the light level reaching the floor, so a taller room generally needs more total lumens. At 8 ft the room index works out at 1.56, giving a utilisation factor of 0.63.

Computed with the lumen method — see how it works and where it is weak. Planning guidance only, not an electrical design. Fixture counts are a starting point — follow your local wiring rules and use a licensed electrician for the installation.